Why a Maglock Does Not Belong on an Exterior Door

A maglock on an exterior door unlocks when power fails. Compare an electric strike, electrified panic hardware, and a mortise lock before you spec the door.

The Short Answer

A maglock on an exterior door unlocks when the power drops. The lock is an electromagnet on the frame and a steel armature on the door. Power on, they bond and the door is held. Power off, there is no latch. If that magnet is the only thing locking the door, anyone can pull it open from the outside. The trade calls this failing open, which means failing unlocked. The door does not swing itself open. Nothing is holding it.

The building code sections that allow this lock on an egress door require that unlock. It is the right behavior for getting people out. It is the wrong behavior for a door that faces a sidewalk or a parking lot. On an exterior door we spec an electric strike, electrified panic hardware, or an electrified mortise lock. The inside still opens by hand with no power. The outside stays locked when the power fails. Commercial access control installation is the reader, the controller, and this hardware decision together.

Why a Maglock Fails Open

A magnetic lock has one state that matters. Energize the coil and the magnet holds the armature. Remove power and the hold is gone. There is no bolt and no mechanical latch in the lock. A cut wire, a failed power supply, a battery that has gone flat, a relay that opens, or a fire alarm release all end the same way. The door is unlocked from both sides.

A battery on the access control power supply does not change that. It keeps the coil energized until the battery is exhausted. A fire alarm release opens the lock circuit even while the battery is healthy. Battery backup is a delay. It does not turn a maglock into a lock that stays locked.

An electric strike and an electrified mortise lock can be ordered fail-secure. Power off, the outside stays locked. The person inside does not need that power. The inside lever, or the panic bar, retracts the latch mechanically. That hardware is not stuck in the "must unlock when power fails" rule, because leaving the building does not depend on the coil letting go.

Adding a maglock on top of a door that already has a latch is not extra security. The person leaving then has two devices that both have to release. Egress hardware is one obvious operation. If the door already latches, we electrify that latch. We do not stack a magnet on the header and call it done.

What the Egress Rules Require

A maglock on a door people use to leave the building is a special locking arrangement. The section number is not one number. It depends on which book the city adopted, and on how the maglock lets people out. There are two release methods in the model codes.

  • Sensor release. A sensor on the egress side sees a person approaching and unlocks the magnet. This is the request-to-exit sensor mounted over the door.
  • Door hardware release. A switch in the lever, the touch bar, or the panic device cuts power to the magnet when someone operates that hardware.

Both methods still require the maglock to unlock when its power is lost. Meeting the section means the door is legal to exit through. It does not mean the door stays secure against the street during an outage.

These are the adoptions for Brentwood, for Metro Nashville, and for buildings under the Tennessee State Fire Marshal. Other cities adopt their own editions. Confirm the book on the permit. Local amendments exist, and the inspector's adopted code is the one that counts.

WhereAdopted bookSensor releaseDoor hardware release
City of Brentwood2018 IBC1010.1.9.91010.1.9.10
City of Brentwood2018 NFPA 1017.2.1.6.27.2.1.5.6
Metro Nashville2024 IBC1010.2.111010.2.10
Tennessee State Fire Marshal2021 IBC1010.2.121010.2.11

The City of Brentwood publishes the 2018 International Building Code for commercial work, and the Brentwood Fire Department has adopted the 2018 NFPA 101 Life Safety Code. The two books use different section numbers for the same two ideas. On the 2018 Life Safety Code, door hardware release is 7.2.1.5.6. In that 2018 book, 7.2.1.6.3 is elevator-lobby locking, not a maglock section. The 2021 edition of NFPA 101 moved door hardware release to 7.2.1.6.3. Brentwood is on the 2018 book, so the 2021 number does not go on a Brentwood drawing.

Metro Nashville lists the 2024 International Building Code as adopted. In that edition the numbers shifted again: door hardware release is 1010.2.10 and sensor release is 1010.2.11. The 2021 IBC numbers are the neighbors of those, and they are not interchangeable. Door hardware release is 1010.2.11 in the 2021 book and 1010.2.10 in the 2024 book.

The Tennessee State Fire Marshal adopted the 2021 IBC effective April 17, 2025, for buildings under the state's jurisdiction. A normal commercial door there is an IBC question: door hardware release in 1010.2.11, sensor release in 1010.2.12. Where a city has adopted its own code, that book controls, which is why Brentwood and Nashville are in the table on their own.

The adoption pages:

The sensor-release sections share a list of conditions. This is the 2021 IBC text at 1010.2.12 and the 2024 IBC text at 1010.2.11. The 2018 IBC section, 1010.1.9.9, is the same kind of rule.

  • The sensor is on the egress side, arranged to detect a person approaching, and that detection unlocks the lock.
  • Loss of power to the sensor unlocks the lock.
  • Loss of power to the lock unlocks the lock.
  • A manual release, signed PUSH TO EXIT, mounted 40 to 48 inches above the floor and within 5 feet of the door. Operating it has to interrupt power to the lock directly, independent of the access control electronics, and the lock stays unlocked for at least 30 seconds.
  • Where the building has a fire alarm, alarm activation unlocks the lock until the alarm is reset. Where a sprinkler system or a fire detection system is provided, that activation unlocks the lock until reset as well.
  • Emergency lighting on the egress side of the door.
  • Locking hardware listed to UL 294. The 2024 IBC, which Nashville has adopted, also allows the locking device to be listed to UL 1034.

Door hardware release is a shorter list. The hardware is mounted on the door, the operation is obvious, and a person can work it with one hand. Operating it cuts power to the lock immediately. Loss of power to the locking system unlocks the door. Where panic hardware or fire exit hardware is required, operating that hardware also releases the lock. These sections do not require the separate push button, and they do not require the fire alarm to drop the lock. A jurisdiction can ask for those extras. The model text does not.

One 2024 change matters in Nashville. A door that is required to have panic hardware is no longer a sensor-release door under the 2024 IBC. The release has to come from a switch in the panic hardware, which is section 1010.2.10. Panic hardware is required on doors that serve Group A or Group E spaces with an occupant load of 50 or more. Brentwood's 2018 books still describe both release methods.

The IBC sections in the table do not permit this arrangement in Group H.

An electric strike, an electrified mortise lock, or electrified panic hardware that still opens from the inside with no power is not in these sections. The person leaving does not depend on a sensor, and does not depend on power being removed. The electric part only decides who can come in. That is the hardware an exterior door should use.

Need help with this?

Call (629) 280-2800 or request a free assessment. We respond within one business day.

Where Request-to-Exit Sensors and Push Buttons Go Wrong

"Request to exit" gets used for two different devices, and only one of them unlocks a maglock.

One sensor shunts the door-position alarm. Someone leaves, the door opens, and the access control system does not treat it as a forced door. That sensor does not drop the magnet. The other device is the unlock sensor the sensor-release section is written around. If the only thing over the door is an alarm shunt, people walk up to a door that stays locked.

A passive infrared unlock sensor misses people, and it trips when it should not. A person approaching along the latch side, someone who stops short of the beam, a path that never crosses the pattern, a cart or a stack of boxes between the person and the sensor: the magnet is still holding when they reach the door. The same sensor unlocks the door for a heater blowing across the pattern, sun load through a glass storefront, or someone walking past inside the lobby. Each of those trips is an exterior door with no hold.

The push button is the backup, and it is the part that fails inspection when it is wired as a request to the controller. The sensor-release text says the button has to interrupt power to the lock directly, independent of the access control electronics. A contact that only lands on a controller input leaves the door locked if that controller is dead, frozen, or programmed to ignore the input. The button also has to be where a person can use it: 40 to 48 inches above the floor, within 5 feet of the door, signed PUSH TO EXIT, and clear of the door swing, a sidelight, or a planter. Once it is pressed, the lock stays unlocked for at least 30 seconds. On a street door, that is 30 seconds with no credential required. We check the wording, the height, and the direct power interrupt before we call the door done. A button at the wrong height, or a button labeled with some other phrase, is not the device the section describes.

The Fire Alarm Release Belongs to the Fire Alarm Contractor

Where the sensor-release section applies and the building has a fire alarm, alarm activation has to unlock the maglock and hold it unlocked until the alarm system is reset. The sprinkler system or the fire detection system, where the building has one, does the same thing. That interface is fire alarm work.

ICTAlly does not design, install, or monitor fire alarm systems. The fire alarm contractor provides the relay and the reset behavior, and the release is tested on their inspection. We land the lock power so that relay actually opens the magnet circuit. We do not put the release only in access control software. A rule in the panel that is supposed to unlock on fire can miss the alarm, get bypassed, or die with the panel. The push-button rule is the same idea: the interruption has to be independent of the locking electronics. A listed relay from the fire alarm system, opening lock power, is the coordination we set up with the contractor who owns that system.

While that alarm is active, an exterior maglock is unlocked from the street. Resetting the alarm is what locks the door again. A door-hardware-release maglock is not required by these model sections to drop on fire alarm. It still drops when its own power drops. Neither arrangement is what you want on a door that should stay locked against the outside during an alarm or an outage.

Weather, Alignment, and Holding Force

The holding force printed on a maglock is a lab number. Full face contact, clean metal, coil at the voltage the lock was built for. Most of these locks are 12 or 24 volt DC coils. An exterior door fights all three assumptions.

The armature has to meet the magnet flat. It is built to float a little on its mount so it can seat. Bolt it rigid, or let the door sag, and one corner touches. Exterior doors sag. Closers drift out of adjustment. Wind racks an aluminum storefront. A hollow-metal door twists over a season. A gap at one corner of the armature gives up most of the hold the label was measured at. The label was not measured on a crooked door.

Weather sits in that joint. Dust, a film of rain, ice, and rust on an armature that lives outside keep the two faces from bonding. A maglock does not seal the door and it does not shed water. It only pulls when the metal is clean and touching.

Voltage counts at the coil, not at the power supply in the closet. A long run of wire that is too small, or one supply shared across too many locks, delivers less than the coil was built for. The door will push open while the label still reads what it read on the bench. We meter the lock under load before we accept the hold.

A shear maglock, mortised into the top of the door and the header, fails unlocked the same way and tolerates even less misalignment. It is a maglock with a tighter installation. It is not a fix for an exterior door.

Maglock vs Electric Strike, Panic Hardware, and a Mortise Lock

Three locks keep an exterior door locked from the outside when the power fails, and still let someone leave with no power. Pick from the door that is actually in the opening.

Electric strike, fail-secure

The strike replaces the plate the latch falls into. A valid credential releases the strike so the latch can pull free. Power off, a fail-secure strike stays closed and the outside stays locked. The inside lever or the panic device still retracts the latch with no power. The strike has to match the latch. A cylindrical lock, a mortise lock, and an aluminum storefront door are three different strikes. The faceplate, the cavity depth, and the fail mode all have to fit that frame. A fail-safe strike on a street door has the same outage problem as a maglock: power off, the outside is open. Fail-secure is the function for an exterior door. A stair door that has to unlock so people can re-enter is a different door, and it is usually not the street entrance.

Electrified panic hardware

Where the door is required to have panic hardware or fire exit hardware, this is the device those rules are written around. Electric latch retraction pulls the latch when the system grants entry. Electrified trim unlocks the outside. Pushing the bar still retracts the latch mechanically, with power or without it. In Nashville, under the 2024 IBC, a door that requires panic hardware is not a place for a sensor-release maglock. We put the electric function in the exit device and leave the magnet off the header.

Electrified mortise lock

Ordered fail-secure, the inside lever always retracts the latch, and the outside lever unlocks on a valid credential. Power loss leaves the outside locked and the inside free. It belongs on a door prepped for a mortise lock, which covers a lot of commercial hollow-metal and wood doors. It is a poor retrofit for an aluminum storefront that was never prepped for a lock body.

All three still get a door-position switch, so a door left open reports. The switch is not the lock. Aluminum storefront is the opening that gets a maglock because cutting a lock pocket in the frame is unpopular. Strikes and exit devices are made for those frames. Specify that hardware before anyone drills the header for a magnet.

When a Maglock Is Still a Fair Choice

Some interior doors. A glass office door with no lock prep, a cross-corridor door, a suite door where the security line that matters is the exterior and an unlocked door during an outage is acceptable. If that interior door is still a means of egress, it still has to meet the sensor-release section or the door-hardware-release section of the code adopted at that address: listed hardware, unlock on loss of power, and the release method that section names. An interior door that is not an egress door, a closet or a private office that is not a required exit, is a hardware choice. A maglock there is reasonable when you want the door to unlock if the power fails and the frame gives you nowhere to put a strike.

The street door, the door from a parking garage into the lobby, and any other door you need locked against the outside during an outage or a fire alarm are not that case. Those get a latch that stays locked from the outside when the power supply is dead.

Frequently Asked Questions

Can you put a maglock on an exterior door?

You can mount one. If the door is there to keep people out, it is the wrong lock. A maglock fails unlocked when power is lost, and the egress sections that allow it on a means of egress require that unlock. An electric strike in fail-secure mode, electrified panic hardware, or an electrified mortise lock keeps the outside locked in an outage and still lets people leave by hand. In the City of Brentwood the adopted books are the 2018 IBC and the 2018 NFPA 101. In Metro Nashville it is the 2024 IBC. Where the Tennessee State Fire Marshal is the authority, it is the 2021 IBC.

What is the difference between a maglock and an electric strike?

A maglock holds the door with an electromagnet and has no latch. Power off, the door is unlocked from both sides. An electric strike works with a real latch. In fail-secure mode the strike stays locked when power fails, so the outside stays shut, and the inside lever or panic bar still retracts the latch mechanically. The strike has to match the lock and the frame. A fail-safe strike unlocks on power loss and has the same problem on an exterior door that a maglock has.

Does a maglock unlock during a power outage?

Yes. No power to the coil means no hold. A battery on the power supply only delays that until the battery is exhausted, and a fire alarm release opens the circuit even while the battery is up. The egress sections for this kind of lock require the unlock when lock power is lost.

Does a maglock have to release when the fire alarm trips?

Under the sensor-release section, yes, if the building has a fire alarm. The alarm has to unlock the lock and hold it unlocked until the alarm is reset. The sprinkler or fire detection system does the same where the building has one. Door hardware release, the switch in the lever or the panic bar, does not add that fire alarm requirement in the IBC and NFPA 101 sections above. The tie-in itself is fire alarm work. ICTAlly does not design, install, or monitor fire alarm systems. We coordinate the lock power so the fire alarm contractor's relay drops the magnet.

When is a maglock a reasonable choice?

On some interior doors, where an unlocked door during an outage is acceptable and the frame has no decent place for a strike. If that door is a means of egress, it still has to meet the sensor-release or door-hardware-release section adopted for that address. An exterior door, including the door from a garage into the building, gets a latch that stays locked from the outside when the power fails.

Specify the Lock Before the Wire Is Pulled

ICTAlly is a veteran-owned low-voltage contractor in Brentwood. We install commercial access control across Middle Tennessee, and the lock on each door is part of that job. Access control work is under Tennessee Alarm Contractor License #2663. That license is Tennessee only. We do not design, install, or monitor fire alarm systems. When a door needs a fire alarm release, the fire alarm contractor owns that relay and we coordinate the lock circuit with them.

Request a site walk or call (629) 280-2800.

T

Theodore, Founder

Veteran-owned and headquartered in Brentwood, TN. Theodore founded ICTAlly to bring military-grade discipline to low voltage contracting: showing up on time, doing the work to standard, and standing behind every installation. ICTAlly serves commercial clients across Nashville and Middle Tennessee.

Need Help With Your Infrastructure?

Free on-site assessment for businesses across Nashville and Middle Tennessee.